From: "Saved by Internet Explorer 11" Subject: Output Transformers Date: Tue, 24 May 2016 15:46:31 -0700 MIME-Version: 1.0 Content-Type: text/html; charset="Windows-1252" Content-Transfer-Encoding: quoted-printable Content-Location: http://www.geofex.com/ampdbug/outtrans.htm X-MimeOLE: Produced By Microsoft MimeOLE V6.1.7601.17609 Output Transformers=20 =20

Testing Output Transformers

Back to = the top=20 of the Amp Debugging Page Back to the GEO Home=20 Page

You can fairly quickly determine if a transformer is grossly bad. = This does=20 not say anything about the subtleties of it's tone, only that it is = functioning. Tests of relative tonal "goodness" are also possible, but require a lot = of equipment and experience to do correctly. For the tests described = here,=20 you'll need an ohmmeter for the simplest testing, and for more advanced = tests, =20 a means of measuring AC voltage and current simultaneously, such as a = pair of=20 VOMs or DMMs, and a 110/120 to 6.3VCT filament transformer, and either a = variac (variable transformer) or a light bulb socket in series with the = primary of the=20 filament transformer to limit the power you put into the transformer = under test.=20

If you do the advanced tests, be aware:
Both the filament = transformer and=20 the transformer under test will have at least AC line voltage on them, = an may=20 well have much higher voltage, several hundred volts on one or more = windings. =20 You are therefore in danger of being KILLED if you are = not both=20 knowledgeable and careful about how you do these tests. These tests are = clearly=20 hazardous as defined in the warnings section of this page.

Simple Tests

Unplug the amp and drain the capacitors before you start. Do not = remove the=20 transformer from the amplifier before you start. Remove the output and=20 rectifier tubes.

Identify which wires are which by circuit connection. The primary = will have=20 two (single ended), three (push pull, or very rarely single ended with = ultra=20 linear tap), or five (push pull with ultralinear taps) leads. Noting = which=20 leads connect to the B+ line, measure the resistance from the B+ lead to = each=20 plate of the output tube(s). Write the resistance reading down. Measure = the=20 other side if it's puah pull. Plate windings are almost always in the = tens to a=20 few hundred ohms of resistance. A reading much over 1K is pretty sure = sign that=20 the winding is burned open. If it's open, the transformer is dead. = [There are=20 ways to fix "slightly-dead" transformers, but this is extremely risky, = and=20 probably doomed to failure. I'm not going to write down how. Don't = waste your=20 time.]

While you're at it, measure the resistance of every lead to the = chassis. This=20 reading should be very high, hundreds of K or preferably megohms. A low = reading=20 here indicates a short to the transformer core - again, dead = transformer.

Do a similar test on the secondaries - look for open windings, or = shorts to=20 the core. Finally, test for the resistance from primary to secondary. A = low value, under a few K indicates an internal short, and a dead = transformer.

If the transformer fails any of the simple test, it's dead. Replace = it. If=20 it passes all of the simple tests, it may still have an internal short = Sometimes=20 a primary will have enough resistance that the transformer does not burn = up or=20 burn the wires in two , but will just bog down, have low power and sound = bad. If=20 you suspect that is the case and you don't have the skills to do the = advanced=20 tests, take it to a competent tech.

Advanced Tests

Do the shorts/opens tests above first.
Then:
Identify a = secondary=20 winding, 8 ohm tap if it's available, and hook up one and only one = winding to=20 either 1/2 of the 6.3VCT or to the variac. Make D^&%ED sure the = variac is=20 all the way down if you're using one of those. Make sure that no other = leads are=20 connected (or shorted together, or touching your screwdriver on your = bench=20 or... well, you get the idea). Check for safety load resistors on the = output=20 jacks or secondary windings. These can cause you to erroneously think it = is bad.=20 There must be no loads on any winding. Put your voltmeter on the = winding, and=20 the current meter to measure the AC current through it, hook up the = 3.15 VAC=20 source, and turn on the AC - not to the amp, but to the AC feeding the = winding=20 you're driving. The voltmeter should measure 3.15 (or close) volts AC, = the=20 light bulb (if used) should NOT be lit brightly, and nothing should be = humming=20 or smoking ;-). There should be only a little current going through = the=20 winding. If the voltage is lower than 3 volts, or you are pulling amps = of=20 current, then there is a load on the transformer, internally since you = have=20 disconnected all the leads, meaning that there is an internal short. = (Which=20 means that you ought to be sure that there is no other load on the = transformer,=20 because you're going to throw it away if it has an internal short - be = sure=20 you're right!)

If all is well, no smoke, flames, loud hum, poultergeists, or = lightning,=20 measure the voltage that now appears on the other windings. The = voltages will=20 be equal to the ratios of the voltages that will appear on these = windings in=20 normal operations. For the primaries of output tubes, this can be up to = a couple=20 of hundred volts, so don't think that you can relax your safety = precautions - it=20 can still kill you, even driven with 3VAC on the secondary of the = output=20 transformer. The half-primaries of the output transformer should have = identical=20 voltages on them. Secondaries should have multiples of the voltage = you're putting on the tap you chose. If you used an 8 ohm tap, a 4 ohm tap = will have about 2.3VAC on it, a 2 ohm tap will have 1.6VAC on it, and a 16 ohm = tap will=20 have about 4.5VAC on it.

If the transformer passes all these tests, it's almost certainly = good.=20